USB-COMi RS-485 Connection Diagram
 
Troubleshooting:

The diagram above is intended to cover as many different host RS-485 serial port designators as possible. The Data line on every DGH module is RS-485 data positive (+) line and the Data* line is data minus (-). Use the following list to further assist with RS-485 communications problems.

1. Using a voltmeter, measure the power supply voltage at the +Vs and GND terminals to verify the power supply voltage is between +10 and +30Vdc.

2. Verify using an ohmmeter that there are no breaks in the communications data lines.

3. Confirm software communications settings in Host computer match those values being used by the connected module(s).

4. If the Baud Rate value being used in the application is greater than 300 Baud and the module will only communicate 300 Baud then make sure that the DEFAULT* terminal is not connected to Ground (GND).

5. If the problem is not corrected after completing the steps above then connect the module by itself to a Host computer as outlined in Chapter 1.0 under "Quick Hook-up". Start the supplied Utility software and please call the factory for further assistance.
 
Modbus Products
ASCII Products
Accessories
Support
Purchase
Company  
  D1000M Series
  D1700M Series
  D3000M Series
  D5000M Series
  DIN-100 Series
  D6000 Series
  D8000 Series
  D1000 Series
  D1700 Series
  D2000 Series
  D3000 Series
  D4000 Series
  D5000 Series
  Mounting Backplanes
  Module Accessories
  Serial Converters
  USB Converter
  Power Supplies
  Software
  Cables
  FAQ's
  Data Sheets
  Diagrams
  User Manuals
  Product Finder
  Modbus Support
  Contact Support
  Product Warranty
  How to Buy
  Shop Online
  International
  View Shopping Cart
  About Us
  Contact Us
  Policies
  Sitemap
  Blog
  Join our Email List

        
 
 
Copyright Dutile, Glines & Higgins Corporation,
All Rights Reserved.